![SOMFY Animeo 1870452 Manual Download Page 29](http://html.mh-extra.com/html/somfy/animeo-1870452/animeo-1870452_manual_1317508029.webp)
animeo KNX 4 DC Motor Controller
28.02.2019
WM 24 V DC
2019 Somfy Activités SA
Ref. 5147817A
29/56
value (0%)
value (100%)
6.3.2 Intermediate Position 2 (IP2)
6.3.2.1 Up/Down position (0-100%)
Default value:
0 % (function disabled)
Selection options:
0 - 100 %
With this parameter the intermediate position 2
“UP/DOWN” is defined. The set value in % refers to the
parameterized move times of the corresponding blind of the menu index
cards Motor 1…4/Motor 1-4.
If the IP UP/Down position parameter is set to 0 %, the IP position is disabled. This function avoids any
movement of the blinds by using the “my” or IP push button.
6.3.2.2 Slat position (0-100%)
Default value:
0 %
Selection options:
0 - 100 %
With this parameter the intermediate position 2
“Slats” is defined. The set value in % refers to the parameter-
ized complete slats turn of the corresponding Venetian blind
of the menu index card Motor 1…4/Motor 1-4.
6.3.3 Block position orders (1 Byte) and IP2
Default value:
No
Selection options:
No
Yes
Position orders (byte) can be blocked per object (51-54) using this parameter. If a telegram with the value
“1”
is received on the corresponding object during a blinds move, this move is carried out up to the end. Only
then are further move commands (byte) blocked. If a telegram with the value
“0” is received on the corre-
sponding object, the move commands (byte) are released again.
6.3.4 Block slat orders (1 Byte)
Default value:
No
Selection options:
No
Yes
Slat orders (byte) can be blocked per object (51-54) using this parameter. If a telegram with the value
“1” is
received on the corresponding object when the Venetian blind is turning, this move is carried out up to the
end. Only then are further slat orders (byte) blocked. If a telegram with the value
“0” is received on the corre-
sponding object, the slat orders (byte) are released again.
6.3.5 Block Up/Down (1 Bit) and Intermediate Position 1 (IP 1)
Default value:
No
Selection options:
No
Yes
UP/DOWN orders (bit) can be blocked per object (51-54) using this parameter. If a telegram with the value
“1” is received on the corresponding object during a blinds move, this move is carried out up to the end. Only
then are further UP/DOWN orders (bit) blocked. If a telegram with the value
“0” is received on the corre-
sponding object, the UP/DOWN orders (bit) are released again.