3 Wiring diagramm
The
“US”-LED blinks regularly when the mains (24 V) and the KNX bus voltage are
connected actively on the device. The device is ready for operation when the
“US”
LED blinks.
Connecttion to …
Cable
Twisted pair
Max. length
Stripping
length
Motors
Min.: 2 x 0.6 mm/22 AWG
Max.: 2 x 2.5 mm
2
/13 AWG
-
6 mm
/0.24‘‘
Switch
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 2.5 mm
2
/13 AWG
Recommended
100 m/330 ft
6 mm/0.24’’
Group control
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 1.5 mm
2
/15 AWG
Recommended
100 m/330 ft
6 mm/0.24’’
KNX-Bus
2 x 0.8 mm/20 AWG
Required, according
to KNX guidelines
6 mm/0.24’’
24 V DC
Min.: 2 x 1.5 mm
2
/15 AWG
Max.: 2 x 2.5 mm
2
/13 AWG
-
10 m/33 ft
6 mm/0.24’’