13.5 AC INPUT
Current input of controller must be connected to outside current transformer. And the current
transformer‘s secondary side current must be 5A. At the same time, the phases of current transformer
and input voltage must correct. Otherwise, the current of collecting and active power maybe not correct.
NOTE: ICOM port must be connected to negative pole of battery.
WARNING! When there is load current, transformer’s secondary side prohibit open circuit.
13.6 WITHSTAND VOLTAGE TEST
CAUTION! When controller had been installed in control panel, if need the high voltage test, please
disconnect controller’s all terminal connections, in order to prevent high voltage into controller and damage it.