HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 18 of 60
6
PROTECTION
6.1
WARNINGS
When controllers detects the warning signals, alarm only and not stop the genset.
Table 8 - Warning Alarms
No.
Type
Description
1
Over Speed
When controller detects the speed is higher than the set value, it will
send warn signals.
2
Under Speed
When controller detects the speed is lower than the set value, it will
send warn signals.
3
Loss of Speed Signal
When controller detects the speed is 0 and the ac
tion select ―Warn‖, it
will send warn signals.
4
AC Over Frequency
When controller detects the frequency of AC genset is higher than the
set value, it will send warn signals.
5
AC Under Frequency
When controller detects the frequency of AC genset is lower than the
set value, it will send warn signals.
6
AC Over Voltage
When controller detects the voltage of AC genset is higher than the set
value, it will send warn signals.
7
AC Under Voltage
When controller detects the voltage of AC genset is lower than the set
value, it will send warn signals.
8
AC Over Current
When controller detects the current of AC genset is higher than the set
value and the action select
―Warn‖, it will send warn signals.
9
Fail to Stop
When generator not stops
after the ―stop delay‖ is over, it will send
warn signals.
10
Charge Alt Fail
When controller detects the charger voltage is lower than the set
value, it will send warn signals.
11
Battery High Voltage
When controller detects the battery voltage is higher than the set
value, it will send warn signals.
12
Battery Low Voltage
When controller detects the battery voltage is lower than the set value,
it will send warn signals.
13
Maintenance Due
When count down time is 0 and the action select ―Warn‖, it will send
warn signals.
14
AC Reverse Power
When controller detects the reverse power value (power is negative) is
higher than the set value and the action select
―Warn‖, it will send
warn signals.
15
AC Over Power
When controller detects the reverse power value (power is positive) is
higher than the set value and the action select
―Warn‖, it will send
warn signals.
16
ECU Warn
When controller gets the alarm signals from engine via J1939, it will
send warn signals.