consumption, total fuel consumption and so on. (Different engine with different parameters)
★
AC
Gen
, including as below,
Phase voltage, Line voltage, frequency, phase sequence.
★
AC
Load
, including as below
Current of each phase, each phase and total active power (positive and negative), each phase and total
reactive power (positive and negative), each phase and total apparent power, each phase and average
power factor (positive and negative), accumulated energy earth current and user A and user B
accumulated energy. .
NOTE: Power factor shows as following,
Remark:
P stands for active power
Q stands for inactive power
Table 7 Power Factor Descriptions
★
DC GEN
, including as below,
Voltage, current, power and accumulated energy
★
Alarm:
Display all alarm information, including warning, alarm shutdown, trip shutdown and trip.
NOTE: For ECU warning and shutdown alarms, if the detailed alarm information is displayed, check engine
according to it, otherwise, please check the manual of generator according to SPN alarm code.
★
Event log
Records all start/stop events (shutdown alarm, trip and stop alarm, manual /auto start or stop) and the real
time when alarm occurs.
★
Others
, including,
Time and Date, count down time for maintenance, input/output ports status, NET status etc.
★
About,
including,
Issue time of software and hardware version and PD number of controller
Power factor Conditions Active power Inactive power
Remark
COS>0L
P>0,Q>0
Input
Input
Load is inductive resistance.
COS>0C
P>0,Q<0
Input
Output
Load is capacitance resistance.
COS<0L
P<0,Q>0
Output
Input
Load equal to one under excitation
generator
COS<0C
P<0,Q<0
Output
Output
Load equal to one over excitation generator.
Remark:
1. Input active power, generator or mains supply electricity to load.
2. Output active power, load supply electricity to generator or mains.
3. Input reactive power, generator or mains send reactive power to load.
4.