HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 26 of 60
No.
Function
Cable Size
Remarks
41
AC Gen A-Phase Volt
Input
1.0mm
2
Connected to A-phase of AC gen-set (2A fuse is
recommended)
42
AC Gen B-Phase Volt
Input
1.0mm
2
Connected to B-phase of AC gen-set (2A fuse is
recommended)
43
AC Gen C-Phase Volt
Input
1.0mm
2
Connected to C-phase of AC gen-set (2A fuse is
recommended)
44
AC Gen N-Line Volt
Input
1.0mm
2
Connected to N-line of AC gen-set
45
AC CT A-Phase Input
1.5mm
2
External connected to secondary coil of current
transformer(rated 5A)
46
AC CT B-Phase Input
1.5mm
2
External connected to secondary coil of current
transformer(rated 5A)
47
AC CT C-Phase Input
1.5mm
2
External connected to secondary coil of current
transformer(rated 5A)
48
AC CT COM
1.5mm
2
See following installation instruction
49
Earth Current
1.5mm
2
External connected to secondary coil of current
transformer(rated 5A)
50
1.5mm
2
51
Aux. Input 8
1.0mm
2
Ground connected is active (B-)
Details see Table
15
52
Aux. sensor 1
1.0mm
2
Connected to temperature, oil
pressure or fuel level sensors
Details see Table
16
53
Aux. sensor 2
1.0mm
2
54
Oil pressure sensor
1.0mm
2
Connected to oil pressure sensor
55
Temperature sensor
1.0mm
2
Connected to temperature sensor
56
Fuel level sensor
1.0mm
2
Connected to fuel level sensor
57
VOUT(+5V)
1.0mm
2
+5V output, using to supply power for voltage type
sensor.
58
Sensor COM
/
Sensor common port, controller internal has been
connected to negative of battery.
59
RS232 COM
0.5mm
2
RS232 port
60
RS232 RX
0.5mm
2
61
RS232 TX
0.5mm
2
NOTE:
USB ports in controller rear panel are programmable parameter ports, user can directly configure controller
via PC.
NOTE:
Ethernet ports in controller rear panel are website port, user can directly configure and monitor controller via
PC.