HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 21 of 60
No.
Type
Description
14
AC Reverse Power
Shutdown
When controller detects reverse power value of AC genset (power
is negative) is higher than the set value, and the reverse power
action select ―shutdown‖, it will send stop signals.
15
AC Over Power
Shutdown
When controller detects reverse power value of AC genset (power
is positive) is higher than the set value, and the reverse power
action select ―shutdown‖, it will send stop signals.
16
DC Over Voltage
When controller detects the voltage value of DC genset is higher
than the set value, it will send stop signals.
17
DC Under Voltage
When controller detects the voltage value of DC genset is lower
than the set value, it will send stop signals.
18
DC Over Current
When controller detects the current value of DC genset is higher
than the set value, it will send stop signals.
19
DC Over Power
Shutdown
When controller detects reverse power value of DC genset (power
is positive) is higher than the set value, and the reverse power
action select ―shutdown‖, it will send stop signals.
20
Temp. Sensor Open
When controller detects sensor is open circuit, and the action
select ―shutdown‖, it will send stop signals.
21
High Temp. Shutdown
When controller detects temperature is higher than the set value, it
will send stop signals.
22
Pressure Sensor Open
When controller detects sensor is open circuit, and the action
select ―shutdown‖, it will send stop signals.
23
Low Oil Pressure
When controller detects oil pressure is lower than the set value, it
will send stop signals.
24
Level Sensor Open
When controller detects sensor is open circuit, and the action
s
elect ―shutdown‖, it will send stop signals.
25
Flexible Sensor 1 Open
When controller detects sensor is open circuit, and the action
select ―shutdown‖, it will send stop signals.
26
Flexible Sensor 1 High
When controller detects the sensor value is higher than the max.
set value, it will send stop signals.
27
Flexible Sensor 1 Low
When controller detects the sensor value is lower than the min. set
value, it will send stop signals.
28
Flexible Sensor 2 Open
When controller detects sensor is open circuit, and the action
select ―shutdown‖, it will send stop signals.
29
Flexible Sensor 2 High
When controller detects the sensor value is higher than the max.
set value, it will send stop signals.
30
Flexible Sensor 2 Low
When controller detects the sensor value is lower than the min. set
value, it will send stop signals.
31
Digital Input Port
When digital input port is set as shutdown, and the action is active,