HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 27 of 60
8
SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS
8.1 CONTENTS AND SCOPES OF PARAMETERS
Table 13 - Parameters Contents and Scopes
No.
Items
Parameters
Defaults
Description
DC Generator
1
Work Mode
(0~2)
0
0: DC;
1: AC
2: DC+AC
2
Rated Voltage
(10~30000)V
500
Standard for checking DC generator
over/under voltage.
3
Loading Voltage
(0-100)%
90
Setting value is DC generator rated
voltage‘s percentage. The controller
detects in the preparation of the load
period, and does not enter the normal
running period when the generator voltage
is less than the load voltage.
4
PT Ratio
(10-30000)V/10V
1000
Ratio of the external connected DC voltage
transformer.
5
Rated Current
(10-6000)A
300
Rated full load current of DC generator,
which is used as the standard for load
power.
6
CT Ratio
(10-6000)A/20mA 400
Ratio of the external connected DC current
transformer.
7
Rated Power
(10-6000)kW
100
It is rated power for DC generator, which is
used as the standard for load power.
8
Over Voltage
Shutdown
(0-200)%
120
Setting value is DC generator rated
voltage‘s percentage, delay value (default
1s) can be set.
9
Under Voltage
Shutdown
(0-200)%
80
10
Over Voltage
Warn
(0-200)%
110
Setting value is DC generator rated
voltage‘s percentage, return value (over
voltage default is 105, under voltage
default is 95 ) and delay value (default 5s)
can be set.
11
Under Voltage
Warn
(0-200)%
90
12
Over Current
(0-200)%
110
Setting value is DC generator rated
current
‘s percentage, alarm action (default:
warning) and delay value (default 5s) can
be set.
13
Over Power
(0-200)%
110
Setting value is DC load rated power
‘s
percentage, alarm action (default: warning)
and delay value (default 5s) can be set.
Timers
1
Start Delay
(0~3600)s
1
Time from mains abnormal or remote start