HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 11 of 60
5
OPERATION
5.1
INDICATORS
Table 5 - Alarm Indicators
Alarm Type
Alarm Indicator
No Alarm
Indicator off
Warning
Slow flashing(1time/s)
Trip Alarm
Slow flashing(1time/s)
Shutdown Alarm
Fast flashing(5 times/s)
Trip and Stop Alarm
Fast flashing(5 times/s)
NOTE: Partial indicators description,
Status indicator:
illuminated from crank disconnect to ETS while off during other periods.
Gens normal Indicator
:
It is light on when generator is normal; flashing when generator state is abnormal; off when
there is no generator power.
5.2
KEY FUNCTION
Table 6 - Key Function Descriptions
Icon
Key
Description
Stop
Stop running generator in Auto/Manual mode; Reset
alarms in stop mode; Lamp test (press at least 3 seconds);
During stopping process, press this button again to stop
generator immediately.
Start
Start genset in Manual mode.
Manual Mode
Press this key and controller enters in
Manual
mode.
Auto Mode
Press this key and controller enters in
Auto
mode.
Mute/Reset Alarm
Alarming sound off; If there is trip alarm, pressing the
button at least 3 seconds can reset this alarm.
Close
Can close breaker in manual mode
Open
Can open breaker in manual mode
Set
Enter setting interface