HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 41 of 60
8.2.2. CUSTOM PERIOD OUTPUT
Defined Period output is composed by 2 parts,
period output S1
and
condition output S2
.
While
S1
and
S2
are
TRUE
synchronously,
OUTPUT
;
While
S1
or
S2
is
FALSE
,
NOT OUTPUT
.
Period output S1
, can set generator‘s one or more period output freely, can set the delayed time and
output time after enter into period.
Condition output S2
; can set as any conditions in output ports.
NOTE: when delay time and output time both are 0 in period output S1, it is TRUE in this period.
Example,
Output period: start
Delay output time: 2s
Output time: 3s
Condition output contents: output port 1 is active
Close when condition output active/inactive: close when active (disconnect when inactive);
Output port 1 active, after enter ―starts time‖ and delay 2s, this defined period output is outputting, after 3s, stop outputting;
Output port 1 inactive, defined output period is not outputting.
8.2.3. CUSTOM COMBINED OUTPUT
Defined combination output is composed by 3 parts, condition output S1 or S2 and condition output S3.
S1
or
S2 is
TRUE
, while S3 is
TRUE
, Defined combination output is outputting;
S1
and
S2 are
FALSE
, or S3 is
FALSE
, Defined combination output is not outputting.
NOTE: S1, S2, S3 can be set as any contents except for “defined combination output” in the output setting.
NOTE: 3 parts of defined combination output (S1, S2, S3) coul
dn’t include or recursively include
themselves.
Example,
Contents of probably condition output S1: output port 1 is active;
Close when probably condition output S1 is active /inactive: close when active (disconnect when inactive);
Contents of probably condition output S2, output port 2 is active;
Close when probably condition output S2 is active /inactive: close when active (disconnect when inactive);
Contents of probably condition output S3: output port 3 is active;
Close when probably condition output S3 is active /inactive: close when active (disconnect when inactive);
When input port 1 active or input port 2 active, if input port 3 is active, Defined combination output is outputting; If input port 3
inactive, Defined combination output is not outputting;
When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not, Defined combination output is not
outputting.