HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 32 of 60
No.
Items
Parameters
Defaults
Description
2: No action
3
High Shutdown
(0~300)ºC
98
Shutdown when sensor temperature is
higher than this value. Detecting only after
safety delay is over. The delay value
(default: 3s) also can be set.
4
High Warning
(0~300) ºC
95
Warn when sensor temperature is higher
than this value. Detecting only after safety
delay is over. The delay value (default: 5s)
and return value (default: 93) also can be
set.
5
Low Warning
(0~1)
0
0: Disable; 1: Enable
6
Custom Curve
Users can configure it according to
sensor
‘s performance.
Oil Pressure Sensor
1
Curve Type
(0~15)
9
SGD See Table 16.
2
Open Circuit
Action
(0~2)
0
0: Warning 1: Shutdown
2: No action
3
Low Shutdown
(0~1000)kPa
103
Shutdown when oil pressure is lower than
this value. Detecting only after safety delay
is over. The delay value (default: 3s) also
can be set.
4
Low Warning
(0~1000)kPa
124
Warn when oil pressure is lower than this
value. Detecting only after safety delay is
over. The delay value (default: 5s) and
return value (default: 138) also can be set.
5
Custom Curve
Users can configure it according to
sensor
‘s performance.
Level Sensor
1
Curve Type
(0~15)
5
SGH See Table 16
2
Open Circuit Action (0~2)
0
0: Warning; 1: Shutdown; 2: No action
3
Low Warning
(0~300)%
10
Warn when level is lower than this value. It
is detecting all the time. The delay value
(default: 5s) and return value (default: 15)
also can be set.
4
Custom Curve
Users can configure it according to
sensor
‘s performance.
Flexible Sensor 1
1
Flexible Sensor 1
Setting
(0~1)
0
0: Disable 1: Enable; (can be set as
temperature/pressure/ lever sensor).
Flexible Sensor 2
1
Flexible Sensor 2
Setting
(0~1)
0
0: Disable; 1: Enable; (can be set as
temperature/pressure/ lever sensor).
Digital Inputs