![Smartgen HGM8110DC User Manual Download Page 25](http://html1.mh-extra.com/html/smartgen/hgm8110dc/hgm8110dc_user-manual_1297526025.webp)
HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 25 of 60
No.
Function
Cable Size
Remarks
9
Charger(D+)
1.0mm
2
Connected with charger starter‘s D+ (WL) terminals.
Being hang up If there is no this terminal.
10
Aux. Input 1
1.0mm
2
Ground connected is active (B-)
Details see Table
15
11
Aux. Input 2
1.0mm
2
Ground connected is active (B-)
12
Aux. Input 3
1.0mm
2
Ground connected is active (B-)
13
Aux. Input 4
1.0mm
2
Ground connected is active (B-)
14
Aux. Input 5
1.0mm
2
Ground connected is active (B-)
15
Aux. Input 6
1.0mm
2
Ground connected is active (B-)
16
Magnetic Pickup
0.5mm
2
Connected with Speed sensor, shielding line is
recommended. (B-) has already connected with speed
sensor 2
17
MP 2
18
MP 1
19
Aux. Input 7
1.0mm
2
Ground connected is active (B-)
Details see Table
15
20
Aux. Output 4
1.5mm
2
Normally close output, rated 7A
Details see Table
14
21
Public points of relay
22
Normally open output, rated 7A
23
ECU CAN
/
Impedance-120
Ω shielding wire is recommended, its
single-end earthed.
24
ECU CAN H
0.5mm
2
25
ECU CAN L
0.5mm
2
26
CAN2 Common port
/
Impedance-120
Ω shielding wire is recommended, its
single-end earthed.
27
CAN2 H
0.5mm
2
28
CAN2 L
0.5mm
2
29
RS485 Common port
/
Impedance-120
Ω shielding wire is recommended, its
single-end earthed.
30
)
0.5mm
2
31
RS485B(-)
0.5mm
2
32
Aux. Output 5
2.5mm
2
Normally close output, rated 8A
Details see Table
14
33
2.5mm
2
Normally open output, rated 8A
34
2.5mm
2
Relay common port
35
Aux. Output 6
2.5mm
2
Normally open output, rated 8A
36
2.5mm
2
Relay common port
37
DC C
1.0mm
2
External connected to DC positive of current transformer
38
DC Current -
1.0mm
2
External connected to DC negative of current
transformer
39
DC V
1.0mm
2
External connected to DC positive of current transformer
40
DC Voltage -
1.0mm
2
External connected to DC negative of current
transformer