HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 23 of 60
6.4
TRIP ALARM
When controller detects trip alarm, it will break close generator signals quickly, but genset not stop.
Table 11 - Trip Alarms
No.
Type
Description
1
AC Over Current
When controller detects the current value of AC genset is higher
than the set value, and the action select ―trip‖, it will send trip
signals.
2
AC Reverse Power
When controller detects reverse power value (power is negative) is
higher
than the set value, and the action select ―trip‖, it will send a
trip signals.
3
AC Over Power
When controller detects the over power value of AC genset (power
is positive) is higher than the set value, and the action select ―trip‖,
it will send a trip signals.
4
DC Over Current
When controller detects the current value of DC genset is higher
than the set value, and the action select ―trip‖, it will send trip
signals.
5
DC Over Power
When controller detects the over power value of DC genset (power
is positive) is higher than the set value, and the action select ―trip‖,
it will send a trip signals.
4
Digital Input Ports
When digital input por
t is set as ―trip‖, and the action is active, it will
send a trip signals.
5
Earth Fault
When controller detects the earth current of genset exceeds preset
earth fault threshold and the earth fault action select ―trip‖ it will
send a trip signals.