HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 35 of 60
No.
Items
Parameters
Defaults
Description
2
Active Type
(0~1)
0
0: Output(N/O)
1: Output(N/C)
8.2
ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS
8.2.1. ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS FORM
Table 14
– Definition Content of Programmable Output Ports
No.
Type
Description
0
Not Used
1
Custom Period 1
Details of function description please see the following.
2
Custom Period 2
3
Custom Period 3
4
Custom Period 4
5
Custom Period 5
6
Custom Period 6
7
Custom Combined 1
8
Custom Combined 2
9
Custom Combined 3
10
Custom Combined 4
11
Custom Combined 5
12
Custom Combined 6
13
Oil Pre-heat Output
14
Reserved
15
Reserved
16
Reserved
17
Air Flap Control
Action when over speed shutdown and emergence
stop. It also can close the air in flow.
18
Audible Alarm
Action when warning, shutdown, trips. Can be
connected with
annunciator externally. When ―alarm
mute‖ configurable input port is active, it can remove
the alarm.
19
Louver Control
Action in genset starting and disconnect when genset
stopped completely.
20
Fuel Pump Control
It is controlled by fuel pump of level sensor‘s limited
threshold.
21
Heater Control
It is controlled by heating of temperature sensor‘s
setting bound.
22
Cooler Control
It is controlled by cooler of temperature sensor‘s
setting bound.
23
Fuel Pre-supply
Action when start and running safety period.
24
Generator Excite
Output in start period. If there is no generator
frequency during hi-speed running, output for 2
seconds again.
25
Pre-lubricate
Actions in period of pre-heating to safety run.
26
Remote Control
This port is controlled by communication (PC).