HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 22 of 60
No.
Type
Description
Shutdown
it will send stop signals.
32
Earth Fault
When controller detects the earth current of genset exceeds preset
earth fault threshold and the earth fault action select ―shutdown‖ it
will send stop signals.
6.3
TRIP AND STOP ALARM
When controller detects trip and stop alarm signals, it will shutdown generator quickly and stop after
high speed cooling.
Table 10 - Trip and Stop Alarms
No.
Type
Description
1
AC Over Current
When controller detects the current value of AC genset is higher
than the set value, and the action select ―trip and stop‖, it will send
trip and stop signals.
2
Maintenance Due
When count down time is 0 and the action select ―trip and stop‖, it
will send a trip and stop signals.
3
AC Reverse Power
When controller detects reverse power value of AC genset (power
is negative) is higher than the set value, and the action sel
ect ―trip
and stop‖, it will send a trip and stop signals.
4
AC Over Power
When controller detects the over power value of AC genset (power
is positive) is higher than the set value, and the action select ―trip
and stop‖, it will send a trip and stop signals.
5
DC Over Current
When controller detects the current value of DC genset is higher
than the set value, and the action select ―trip and stop‖, it will send
trip and stop signals.
6
DC Over Power
When controller detects the over power value of AC genset (power
is positive) is higher than the set value, and the action select ―trip
and stop‖, it will send a trip and stop signals.
7
Digital Input Ports
When digital input port is set as ―trip and stop‖, and the action is
active, it will send a trip and stop signals.
8
Earth Fault
When controller detects the earth current of genset exceeds preset
earth fault threshold and the earth fault action select ―trip and stop‖
it will send trip and stop signals.