HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 47 of 60
10 SENSORS SETTING
—
When reselect sensors, the sensor curve will be transferred into the standard value. For example,
if temperature sensor is SGX (120°C resistor type), its sensor curve is SGX (120°C resistor type);
if select the SGD (120°C resistor type), the temperature sensor curve is SGD curve.
—
When there is difference between standard sensor curves and using sensor, user can adjust it in
―curve type‖.
—
When input the sensor curve, X value (resistor) must be input from small to large, otherwise,
mistake occurs.
—
If select sensor type as ―None‖, sensor curve is not working.
—
If corresponding sensor has alarm switch only, user must set this sensor as ―None‖, otherwise,
maybe there is shutdown or warning.
—
The headmost or backmost values in the vertical coordinates can be set as same as below,
Fig. 2 - Sensor Carve Setting
Table 18 - Normal Pressure Unit Conversion Form
N/m
2
pa
kgf/cm
2
bar
psi
1Pa
1
1.02x10
-
5
1x10
-
5
1.45x10
-
4
1kgf/cm
2
9.8x10
4
1
0.98
14.2
1bar
1x10
5
1.02
1
14.5
1psi
6.89x10
3
7.03x10
-
2
6.89x10
-
2
1