HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 29 of 60
No.
Items
Parameters
Defaults
Description
Shutdown
and delay value (over speed default: 2s;
under speed default:3s) also can be set.
8
Under Speed
Shutdown
(0~200)%
80
9
Over Speed Warn (0~200)%
110
Setting value is percentage of rated speed
and delay value (default: 5s) and return
value (default: over speed: 108; under
speed: 90) also can be set.
10
Under Speed
Warn
(0~200)%
86
11
Battery Rated
Voltage
(0~60.0)V
24.0
Standard for detecting over/under voltage
of battery.
12
Battery Over
Volt Warn
(0~200)%
120
Setting value is percentage of rated
voltage of battery. Delay value (default:
60s) & return value (default: over voltage:
115; under voltage: 90) also can be set.
13
Battery Under
Volt Warn
(0~200)%
85
14
Charge Alt Failure (0~60.0)V
8.0
In normal running, when charger D+(WL)
voltage under this value, charge failure
alarms.
15
Start Attempts
(1~10) times
3
Max. crank times of crank attempts. When
reach this number, controller will send start
failure signal.
16
Crank Disconnect (0~6)
2
See Table 17
There are 3 conditions of disconnecting
starter with engine. Each condition can be
used alone and simultaneously to
separating the start motor and genset as
soon as possible.
17
Disconnect
Generator Freq
(0~200)%
24
Setting value is percentage of gen rated
frequency. When generator frequency
higher than the set value, starter will be
disconnected. See the installation
instruction.
18
Disconnect
Speed
(0~200)%
24
Setting value is percentage of gen rated
speed. When generator
‘s speed higher
than the set value, starter will be
disconnected. See the installation
instruction.
19
Disconnect Oil
Pressure
(0~1000)kPa
200
When generator oil pressure higher than
the set value, starter will be disconnected.
See the installation instruction.
AC Generator
1
AC System
(0~3)
0
0: 3P4W; 1: 3P3W;
2: 2P3W; 3: 1P2W.
2
Poles
(2~64)
4
Numbers of generator pole, used for
calculating starter rotate speed when