HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 31 of 60
No.
Items
Parameters
Defaults
Description
current.
3
Rated Power
(0~6000)kW
276
Generator‘s rated power, standard of load
power.
4
Over Current
(0~200)%
120
Setting value is percentage of AC
generator rated full load current. Delay
value also can be set as fixed time lag or
inverse time lag.
5
Reverse Power
(0~1)
0
0: Disable 1: Enable
6
Action
(0-3)
0
0: Warning; 1: Shutdown; 3: Trip and Stop;
4: Trip
7
Over Power
(0~1)
0
0: Disable 1: Enable
8
Action
(0-3)
0
0: Warning; 1: Shutdown; 3: Trip and Stop;
4: Trip
Breaker
1
Close Time
(0~20.0)s
5.0
Pulse width of generator switch on. When it
is 0, means output constantly.
2
Open Time
(0~20.0)s
3.0
Pulse width of generator switch off.
3
Check Time
(0~20.0)s
5.0
Time of detecting switch auxiliary contacts
after ATS breaker transferred.
4
Open Check
(0~1)
0
0: Disable 1: Enable
5
Check Fail Warn
(0~1)
1
0: Disable 1: Enable
Module
1
Power on Mode
(0~2)
0
0: Stop mode 1: Manual mode
2: Auto mode
2
Module Address
(1~254)
1
Controller
‘s address during remote
sensing.
4
Language
(0~2)
0
0: Chinese 1: English 2: Other
5
Password
(0~65535)
00318
For entering advanced parameters setting.
6
Time and Date
Current time and date can be set by users.
7
IP Set
(0-1)
1
0: Disable 1: Enable
All the settings about Ethernet (such as IP
address and subnet mask) will active after
the next time power on.
Scheduling And Maintenance Setting
1
Scheduled Run
(0~1)
0
0: Disable; 1: Enable
2
Maintenance
(0~1)
0
0: Disable; 1: Enable
3
Scheduled Not
Run
(0~1)
0
0: Disable; 1: Enable
Sensor
Temperature Sensor
1
Curve Type
(0~15)
9
SGD See Table 16.
2
Open Circuit
Action
(0~2)
0
0: Warning;
1: Shutdown;