HGM8110DC GENSET CONTROLLER USER MANUAL
HGM8110DC Genset Controller 2018-12-27 Version 1.1 Page 36 of 60
No.
Type
Description
27
Reserved
28
Reserved
29
Close Generator
Control generator to take load.
30
Open Breaker
Control generator to off load.
31
Reserved
32
Reserved
33
Start Relay
34
Fuel Relay
Action when genset is cranking and disconnect when
stopped completely.
35
Idle Control
Used for engine which has idles. Close before starting
and open when enter into warming up; Close during
stopping idle process and open when stop is
completed.
36
Speed Raise Relay
Action during in warming up process.
37
Speed Drop Relay
Action between the periods
from ―stop idle‖ to ―failed to
stop‖.
38
Energise to Stop
Used for engines with ETS electromagnet. Close when
stop idle is over and open when pre-
set ―ETS delay‖ is
over.
39
Speed Drop Pulse
Active 0.1s when controller enters into stop idle, used
for control part of ECU dropping to idle speed.
40
ECU Stop
Used for ECU engine and control its stop.
41
ECU Power Supply
Used for ECU engine and control its power.
42
Speed Raise Pulse
Active 0.1s when controller enters into warming up
delay; used for control part of ECU raising to normal
speed.
43
Crank Success
Close when detects a successful start signal.
44
Generator OK
Action when generator is normal.
45
Generator Available
Action in period of generator ok to hi-speed cooling.
46
Reserved
47
Reserved
48
Common Alarm
Action when genset common warning, common
shutdown, common trips alarm.
49
Common Trip and Stop
Action when common trip and stop alarm occurs.
50
Common Shutdown
Action when common shutdown alarm occurs.
51
Common Trip
Action when common trips alarm occurs.
52
Common Warning
Action in common when warning alarm occurs.
53
Reserved
54
Battery Over Voltage
Action when battery‘s over voltage warning alarm
occurs.
55
Battery Under Voltage
Action when battery‘s low voltage warning alarm
occurs.
56
Charge Alternator Failure
Action when charge failure warning alarm occurs.
57
Reserved
58
Reserved