7PG2113/4/5/6 Commissioning & Maintenance
©2012 Siemens Protection Devices Limited
Chapter 6 Page 63 of 77
3.2.2 3 Phase VT fail
Apply 3P balanced nominal voltage and 3P balanced current at a level between the
60VTS Ipps Load
setting and
the
60VTS Ipps Fault
setting. Reduce the balanced Voltage on all 3 phases until the VTS operates at the
60VTS
Vpps
setting. Return the voltage to nominal and ensure that VTS resets.
Reduce the 3P balanced current to a level below the
60VTS Ipps Load
setting. Reduce the 3P balanced voltage
to a level below the operate level above. Gradually increase the 3P balanced current until the VTS operates.
Check that the thermal rating of the relay current inputs is not exceeded during the following test. Increase the 3P
balanced current to a level above the
60VTS Ipps Fault
setting. Reduce the 3P balanced voltage to a level below
the operate level above. Gradually reduce the 3P balanced current until the VTS operates.
Setting
Measured
60VTS Vpps
60VTS Ipps Load
60VTS Ipps Fault
Table 3.2-3
3P VTS
If the VTS can be started from a status input fed from an external source, this functionality should be tested.
Ext_Trig 60VTS
Operation
□
Not Applicable
□
3.2.2.1 Element
Blocking
The VT Supervision can be blocked by Binary Input Inhibit. This functionality should be checked.
Element BI
Inhibits
60VTS
Table 3.2-4
60VTS Element Blocking