7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 36 of 42
2.15 67/67N Directional Overcurrent & Earth Fault
2.15.1 Reference
Parameter
Value
θ
s
Angle setting
-95…+95
°
I
Applied current
In
V
Applied voltage
110 V phase-phase (63.5 V phase-earth)
2.15.2 Operate Angle
Attribute
Value
CA
Characteristic angle (I with respect
to V)
θ
s
,
±
5
°
forward
CA
- 85
°
±
5
°
to
CA
+ 85
°
±
5
°
Operating angle
reverse
(
CA
- 180
°
) - 85
°
±
5
°
to (
CA
- 180
°
) + 85
°
±
5
°
10°C to +55°C
±
5
°
Variation in
characteristic
angle
f
nom
- 3 Hz to
f
nom
+ 2 Hz
±
5
°
2.15.3 Operate Threshold
Attribute
Value
I (p/f)
> 5 % In
I (e/f)
> 10 % In
V (p/f)
> 1 V
Minimum levels for
operation
V (e/f)
> 1 V
2.15.4 Operate and Reset Time
Attribute
Value
Operate time
typically 32 < 40 ms at characteristic angle + element
operate time
Reset time
typically < 65 ms at characteristic angle
2.16 87L Pilot Wire Current Differential
2.16.1 Operate Level
The following sensitivities are shown as a percentage of rated current and are directly applicable to the local relay
of a connected pair when subjected to current injection at the local end only. Settings are typically -15% of
quoted sensitivity.