7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 12 of 42
1.5.2 Emissions
IEC 60255-25
1.5.2.1
Radiated Emissions: Enclosure
Type
Limits at 10 m, Quasi-peak
30 to 230 MHz
40 dB(
μ
V/m)
230 to 1000 MHz
47 dB(
μ
V/m)
1.5.2.2
Radiated Emissions: Conducted
Limits
Type
Quasi-peak Average
0.15 to 0.5 MHz
79 dB(
μ
V) 66
dB(
μ
V)
0.5 to 30 MHz
73 dB(
μ
V) 60
dB(
μ
V)
1.5.3 Immunity
1.5.3.1
Auxiliary DC Supply Variation
IEC 60255-11
Type of Phenomena
Test Specifications Duration
Declared
Operation
0% RV
50ms
(Claimed)
Normal Operation
1
40% RV
200ms
Normal operation
1
except where Dip falls
below the relay minimum voltage then Relay
Restart
2
Voltage Dips
70% RV
500ms
Normal operation
1
except where Dip falls
below the relay minimum voltage then Relay
Restart
2
Voltage Interruptions
0% RV
5s
Relay Reset
2
Alternating
Component In DC
(Ripple)
15% max and min RV
Continuous
Normal operation
1
Max & min RV to 0V
60s
Relay Reset
0V
5minutes
Relay Off
Gradual Shut-down/
Start-up
0V to min & max RV
60s
Relay Restart
2
Reversal of DC
Power Supply polarity
Max reversed RV
1minute
Relay remains off
After correcting polarity, Relay Restart
2
Key:
RV = Residual Voltage Test Value. Two conditions: (a) range voltage low-20% and
(b) range voltage high +20%
1
No effect on relay performance
2
Restart with no mal-operation, loss of data or relay damage
1.5.3.2
High Frequency Disturbance
IEC 60255-22-1
Type Level
Common (longitudinal) mode
2.5 kV
Series (transverse) mode
1.0 kV
1.5.3.3
Electrostatic Discharge
IEC 60255-22-2 Class 4