7PG2113/4/5/6 Commissioning & Maintenance
©2012 Siemens Protection Devices Limited
Chapter 6 Page 67 of 77
Inject 1A of balanced current. Gradually increase imbalance current, operating level should be as follows:
46BC Setting
1P unbalance current
(% of 3P current)
20% 75%
25% 100%
30% 129%
35% 161%
40% 200%
Table 3.4-1
46BC Test Currents
46BC Setting
3P balanced current (A)
1P unbalance current (A)
Measured Unbalance
current
Table 3.4-2
46BC Test Results
Apply 1A 1P unbalance current without 3P balanced current. Measure 46BC operating time.
46BC Delay setting
Measured
Table 3.4-3
46BC Operate Time
3.4.1.1 Element
Blocking
The Broken Conductor element can be blocked by Binary Input Inhibit. This functionality should be checked.
Element BI
Inhibits
46BC
Table 3.4-4
46BC Element Blocking