7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 42 of 42
3.5
74TCS & 74CCS Trip & Close Circuit Supervision
3.5.1 Reference
Parameter
Value
t
d
Delay setting
0, 0.02…60 s
3.5.2 Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
30ms
±
10ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
1 % or
±
10ms
Repeatability
±
1 % or
±
10ms
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
≤
5 %
3.6
81HBL2 Inrush Detector
3.6.1 Reference
Parameter
Value
I
Setting
(Ratio of 2nd Harmonic current to
Fundamental component current)
0.10, 0.11... 0.5
3.6.2 Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
Will pick-up before operation of any protection element due
to magnetic inrush
Reset Time
Will operate until drop-off of any protection element due to
magnetic inrush