7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 41 of 42
3.4
60VTS Voltage Transformer Supervision
3.4.1 Reference
Parameter
Value
V
nps
Vnps Level
7, 8 … 110V
I
nps
Inps Level
0.05, 0.1 … 1 x In
I
pps
Ipps Load Level
0.05, 0.1 … 1 x In
IF
pps
Ipps Fault Level
0.05, 0.1 … 20 x In
V
pps
Vpps Level
1, 2 … 110V
t
d
60VTS Delay
0.00, 0.01…20.00, 20.10… 100, 101… 1000, 1010… 10000,
10100… 14400 s
3.4.2 Operate and Reset Level
Attribute
Value
V
NPSop
Voltage NPS operate level
100 %
V
nps
,
±
5 %
Vn
Voltage NPS reset level
90 %
V
NPSop
,
±
5 %
Vn
V
PPSop
Voltage PPS operate level
100 %
V
pps
,
±
5 %
Vn
Voltage PPS reset level
110 %
V
PPSop
,
±
5 %
Vn
I
NPSblk
Current NPS operate level
100 %
I
nps
,
±
5 % x
In
Current NPS reset level
90 %
I
NPSblk
,
±
5 % x
In
I
PPSblk
Current PPS operate level
100 %
IF
pps
,
±
5 % x
In
Current PPS reset level
90 %
I
PPSblk
,
±
5 % x
In
I
PPSload
Current PPS operate level
100 %
I
pps
,
±
5 % x
In
Current PPS reset level
90 %
I
PPSload
,
±
5 % x
In
Repeatability
±
1 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
≤
5 %
3.4.3 Operate and Reset Time
Attribute
Value
t
basic
Basic operate time 0V to 2 x
Vs
32 ms
±
10ms
Operate time
t
d
+ t
basic
±
1 % or
±
10ms
Repeatability
±
1 % or
±
10ms