7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 16 of 42
2.2.3
Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
1.1 to 0.5 x
Is
: 35 ms,
±
10ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
1 % or
±
10ms
Repeatability
±
1 % or
±
10ms
Overshoot time
< 40 ms
Disengaging time
< 60 ms
2.3
46NPS Negative Phase Sequence Overcurrent
2.3.1 Reference (46DT)
Parameter
Value
I
s
Setting
0.05, 0.06... 4.0
xIn
t
d
Delay setting
0.00, 0.01…20.00, 20.10… 100, 101… 1000, 1010…
10000, 10100… 14400 s
2.3.2 Operate and Reset Level (46DT)
Attribute
Value
I
op
Operate level
100 %
Is
,
±
5 % or
±
1%
In
Reset level
≥
95 %
I
op
Repeatability
±
1 %
Transient overreach
(X/R
≤
100)
≤
-5 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
≤
5 %
2.3.3 Operate and Reset Time (46DT)
Attribute
Value
0 to 2 x
Is
: 40 ms,
±
10ms
t
basic
Element basic operate time
0 to 5 xI
s
: 30 ms,
±
10ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
1 % or
±
10ms
Repeatability
±
1 % or
±
10ms
Overshoot time
<40 ms
Disengaging time
< 60 ms
2.3.4 Reference (46IT)
Parameter
Value
char
Characteristic setting
IEC-NI, -VI, -EI, -LTI; ANSI-MI, -VI, -EI; DTL
Tm
Time Multiplier setting
1.0
I
s
Setting
0.05, 0.06… 2.5
xIn
I
Applied Current (for operate time)
IDMTL
2 to 20 x Is
t
d
Delay setting
0, 0.01… 20 s
t
res
Reset setting
ANSI DECAYING, 0, 1… 60 s