Page 1: ...Surge Protective Devices STV100K Series Instruction Manual ...

Page 2: ......

Page 3: ...or service names are the property of their registered owners 2011 EGS Electrical Group LLC All rights reserved Specifications are subject to change without notice Contents 1 0 Installation 4 1 1 Environment 4 1 2 Mounting 4 1 3 Proper Connection of SPDs 4 1 4 Mechanical Dimensions 5 1 5 Voltage Protection Ratings VPRs 5 1 6 Circuit Ampacity Limitations 5 1 7 Wire Sizing Routing 5 1 8 Wiring Connec...

Page 4: ... 140 F with a relative humidity of 0 to 95 non condensing The unit is provided in a metallic industrial enclosure Do not install in areas with excessive dust corrosive vapors flammable materials or explosive atmospheres 1 2 Mounting Mount the unit as close as possible to the service panel For best performance the unit should be positioned so that the length of the wiring to the surge protec tive d...

Page 5: ... 6 Circuit Ampacity Limitations This device has been investigated by Underwriters Laboratories Inc to with stand without exposing live circuits or components on power sources a voltage of two times 2x the device s ratings and fault currents of up to 65 000 AIC as described in ANSI UL 1449 3rd edition the Standard for Safety Surge Protective Devices SPDs 1 7 Wire Sizing Routing Phase N and GND wire...

Page 6: ...power source of the proper configuration will reduce or impede operation and may result in unit failure NOTES Figure 2 is a three phase wye A three phase delta will have no neutral wire For a three phase delta high leg Phase B will be the high leg A split phase unit will have no Phase C and can be labeled Line 1 and Line 2 A single phase L N unit will have one black phase wire a white neutral wire...

Page 7: ...K 10S Nominal Voltage 120 208 240 V Single phase 3W G Model STV100K 10Y Nominal Voltage 120 208 V Model STV100K 23Y Nominal Voltage 230 400 V Model STV100K 27Y Nominal Voltage 277 480 V Three phase wye 4W G Model STV100K 10X Nominal Voltage 120 208 V Model STV100K 23X Nominal Voltage 230 400 V Model STV100K 27X Nominal Voltage 277 480 V Not UL Listed Contact SolaHD Technical Support for details Th...

Page 8: ...roubleshooting If any of the diagnostic indicators indicate a problem e g red Service LED on and or green LEDs off check all connections and voltages to the unit If all connections are made and reliable and proper voltages are supplied to the unit contact SolaHD Technical Support at 800 377 4384 847 268 6651 or by e mail at solahd technicalservices emerson com 3 0 Registration Warranty 3 1 Product...

Page 9: ...Dimensions W x D x H 6 00 in x 4 00 in x 3 20 in 152 4 mm x 101 6 mm x 81 28 mm Net Weight 8 0 lb 3 63 kg Enclosure Metal NEMA 12 enclosure Connection Mounting Type Parallel Flange Status Indication Red and green LED status indicators audible alarm Form C contacts Safety Approvals UL 1449 3rd edition cULus Listed Warranty 10 years UL 1449 3rd Edition Type 2 Voltage Protection Ratings Line to Neutr...

Page 10: ...ons W x D x H 6 00 in x 4 00 in x 3 20 in 152 4 mm x 101 6 mm x 81 28 mm Net Weight 8 0 lb 3 63 kg Enclosure Metal NEMA 12 enclosure Connection Mounting Type Parallel Flange Status Indication Red and green LED status indicators audible alarm Form C contacts Safety Approvals UL 1449 3rd edition cULus Listed Warranty 10 years UL 1449 3rd Edition Type 2 Voltage Protection Ratings Line to Neutral 1200...

Page 11: ......

Page 12: ...Part Number 80927 Rev 2 January 2011 www solahd com 800 377 4384 847 268 6651 solahd technicalservices emerson com ...