7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 38 of 42
Section 3:
Supervision Functions
3.1
46BC Broken Conductor
3.1.1 Reference
Parameter
Value
NPS to PPS ratio
20,21…100%
t
f
Delay setting
0.03,04,20.0,20.1,100,101,1000,1010…..14400 s
3.1.2
Operate and Reset Level
Attribute
Value
I
curr
Operate level
100 %
I
set
±
5 %
Reset level
90 %
I
curr ,
±
5 %
Repeatability
±
1 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
harmonics to
f
cutoff
≤
5 %
3.1.3
Operate and Reset Time
Attribute
Value
t
basic
Basic operate time 1x In to 0 A
40 ms
Operate time
t
f
+
t
basic
,
±
1 % or
±
20ms
Repeatability
±
1 % or
±
20ms
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
harmonics to
f
cutoff
≤
5 %