7PG2113/4/5/6 Data Communications
©2010 Siemens Protection Devices Limited
Chapter 4 Page 23 of 38
5.2
Implementation Table
The following table identifies which object variations, function codes, and qualifiers the Triangle MicroWorks, Inc.
DNP 3.0 Slave Source Code Library supports in both request messages and in response messages. For static
(non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00
or 01. Requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28. For change-event
objects, qualifiers 17 or 28 are always responded.
In the table below, text shaded as 00, 01 (start stop) indicates Subset Level 3 functionality (beyond Subset Level
2).
In the table below, text shaded as
07, 08 (limited qty)
indicates functionality beyond Subset Level 3.
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Number
Description
Function
Codes (dec)
Qualifier Codes
(hex)
Function
Codes (dec)
Qualifier
Codes (hex)
1
0
Binary Input – Any Variation 1 (read)
22 (assign
class)
00, 01
(start-stop)
06 (no range,
or all)
07, 08
(limited qty)
17, 27,
28(index)
1 1
(default
–
see note
1)
Binary Input
1 (read)
00, 01
(start-stop)
06
(no range, or
all)
07, 08 (limited
qty)
17, 27,
28(index)
129
(response)
00, 01
(start-stop)
17, 28
(index –
see note 2)
1 2
Binary Input with Status
1 (read)
00, 01
(start-stop)
06 (no range,
or all)
07, 08 (limited
qty)
17, 27, 28
(index)
129
(response)
00, 01(start-sto
17, 28
(index –
see note 2)
2
0
Binary Input Change – Any
Variation
1 (read)
06 (no range,
or all)
07, 08 (limited
qty)
2
1
Binary Input Change without
Time
1 (read)
06 (no range,
or all)
07, 08 (limited
qty)
129
(response)
130
(unsol. resp)
17, 28 (index)