7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 7 of 42
1.2.2 AC Current
Nominal
Measuring
Range
In
1 A or 5 A Phase, Earth models
80 x
In
fn
50, 60Hz
47 to 52Hz, 57 to 62Hz
Note. 1A and 5A nominal rating must be specified at the point of ordering.
1.2.2.1
Burden
1.2.2.2
Thermal Withstand
EATS48-5
Overload Current
Phase, Earth and SEF
Overload Period
1A 5A
Continuous 2.0
xIn
10 minutes
3.5
xIn
5 minutes
4.0
xIn
3 minutes
5.0
xIn
2 minutes
6.0
xIn
3 seconds
57.7A
202A
2 seconds
70.7A
247A
1 second
100A
350A
1 cycle
700A
2500A
1.2.3 AC Voltage
Nominal
Operating
Range
Vn
63.5V, 110 V
270 V
fn
50, 60Hz
47 to 52Hz, 57 to 62Hz
1.2.3.1
Burden
Attribute Value
AC Burden
≤
0.02 VA at 63.5 V ,
≤
0.06 VA at 110 V
Value -
Attribute
R Mode
Rf Mode
AC Burden
1.2 VA
3 VA