[7sj6x_anlaufzeitueberwachung-150502-kn, 1, en_US]
Figure 2-56
Logic diagram of the Motor Starting Protection
Switching of Startup Times
The motor manufacturer provides startup time curves for both cold and warm motor conditions (see
). The function Motor Starting Protection automatically performs a switching. The "warm motor"
condition is derived from the thermal storage of the restart inhibit (see Section
2.8.2 Motor Restart Inhibit 66
Therefore, this function must be enabled. The condition for the switching is determined by the parameter
4106
TEMP.COLD MOTOR
. If the motor temperature (actually the rotor temperature) exceeds the threshold
value, then a switching from "cold motor" to "warm motor" takes place (see
). The threshold values
can be derived from the permitted number of cold (n
cold
) and warm (n
warm
) motor startups. By means of the
following formula an approximate limit value can be determined.
(Parameter 4106
TEMP.COLD MOTOR
)
[formel-motoranlauftemperatur-warm, 1, en_US]
The setting value should always be lower than the limit value (see Setting Notes
).
Functions
2.8 Motor Protection
146
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...