Ground Fault Pickup for All Types of Ground Faults (Inverse Time Characteristic Logarithmic Inverse with Knee
Point)
Pickup Current 50Ns
for sensitive transformer
for normal 1-A transformer
for normal 5-A transformer
0.003 A to 0.500 A
0.05 A to 4.00 A
0.25 A to 20.00 A
Increments
0.001 A
Increments
0.01 A
Increments
0.05 A
Minimum time
51Ns T min
0.10 s to 30.00 s
Increments 0.01
s
Pickup current
51Ns I T min
for sensitive transformer
for normal 1-A transformer
for normal 5-A transformer
0.003 A to 1.400 A
0.05 A to 20.00 A
0.25 A to 100.00 A
Increments
0.001 A
Increments 0.01
A
Increments 0.05
A
Knee-point time
51Ns T knee
0.20 s to 100.00 s
Increments
0.01 s
Pickup current
51Ns I T knee
for sensitive transformer
for normal 1-A transformer
for normal 5-A transformer
0.003 A to 0.650 A
0.05 A to 17.00 A
0.25 A to 85.00 A
Increments
0.001 A
Increments 0.01
A
Increments 0.05
A
Maximum time
51Ns T max
0.00 s to 30.00 s
Increments
0.01 s
Time factor
51Ns TD
0.05 s to 1.50 s
Increments
0.01 s
Characteristics
see
Tolerances
Times
inv
5 % ± 15 ms
def.
1 % of setting value or 10 ms
Technical Data
4.17 Ground Fault Detection (Sensitive/Insensitive)
486
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...