Figure 2-11
Logic diagram of the inverse-time overcurrent protection element for phases
If an ANSI characteristic is configured, parameter 1209
51 TIME DIAL
is used instead of parameter 1208
51
TIME DIAL
.
If parameter
MANUAL CLOSE
is set to
51 instant.
and manual close detection applies, the trip is initiated
as soon as the pickup conditions arrive, even if the element is blocked via a binary input.
The same applies to 79 AR 51N inst.
Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
64
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016