No.
Information
Type of
Informa-
tion
Comments
16005
Threshold ΣI^x>
OUT
Threshold Sum Curr. Exponent. exceeded
16009
Resid.Endu. <
LV
Lower Threshold of CB Residual Endurance
16010
Thresh.R.Endu.<
OUT
Dropped below Threshold CB Res.Endurance
16017
ΣI^2t>
LV
Threshold Sum Squared Current Integral
16018
Thresh. ΣI^2t>
OUT
Threshold Sum Squa. Curr. Int. exceeded
Energy Metering
Metered values for active and reactive energy are determined by the device. They can be called up at the front
of the device, read out via the operating interface using a PC with DIGSI, or transferred to a central master
station via the system interface.
Description
Metered Values for Active and Reactive Energy
Metered values of the real power W
p
and reactive power (W
q
) are acquired in kilowatt, megawatt or gigawatt
hours primary or in kVARh, MVARh or GVARh primary, separately according to the input (+) and output (–), or
capacitive and inductive. The measured-value resolution can be configured. The signs of the measured values
appear as configured in address 1108
P,Q VORZEICHEN
(see Section “Display of Measured Values”).
Setting Notes
Setting of parameter for meter resolution
Parameter 8315
MeterResolution
allows increasing the resolution of the energy metered values by the
Factor 10
or
Factor 100
compared to the
Standard
setting.
Settings
Addr.
Parameter
Setting Options
Default Setting
Comments
8315
MeterResolution
Standard
Factor 10
Factor 100
Standard
Meter resolution
Information List
No.
Information
Type of
Informa-
tion
Comments
-
Meter res
IntSP_Ev
Reset meter
888
Wp(puls)
PMV
Pulsed Energy Wp (active)
889
Wq(puls)
PMV
Pulsed Energy Wq (reactive)
916
WpΔ=
-
Increment of active energy
917
WqΔ=
-
Increment of reactive energy
924
WpForward
MVMV
Wp Forward
925
WqForward
MVMV
Wq Forward
928
WpReverse
MVMV
Wp Reverse
929
WqReverse
MVMV
Wq Reverse
2.25.8
2.25.8.1
2.25.8.2
2.25.8.3
2.25.8.4
Functions
2.25 Auxiliary Functions
SIPROTEC 4, 7SJ62/64, Manual
339
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...