Addr.
Parameter
Setting Options
Default Setting
Comments
7140
ZONE SEQ.COORD.
OFF
ON
OFF
ZSC - Zone sequence coordination
7150
50-1
No influence
Starts 79
Stops 79
No influence
50-1
7151
50N-1
No influence
Starts 79
Stops 79
No influence
50N-1
7152
50-2
No influence
Starts 79
Stops 79
No influence
50-2
7153
50N-2
No influence
Starts 79
Stops 79
No influence
50N-2
7154
51
No influence
Starts 79
Stops 79
No influence
51
7155
51N
No influence
Starts 79
Stops 79
No influence
51N
7156
67-1
No influence
Starts 79
Stops 79
No influence
67-1
7157
67N-1
No influence
Starts 79
Stops 79
No influence
67N-1
7158
67-2
No influence
Starts 79
Stops 79
No influence
67-2
7159
67N-2
No influence
Starts 79
Stops 79
No influence
67N-2
7160
67 TOC
No influence
Starts 79
Stops 79
No influence
67 TOC
7161
67N TOC
No influence
Starts 79
Stops 79
No influence
67N TOC
7163
46
No influence
Starts 79
Stops 79
No influence
46
7164
BINARY INPUT
No influence
Starts 79
Stops 79
No influence
Binary Input
7165
3Pol.PICKUP BLK
YES
NO
NO
3 Pole Pickup blocks 79
Functions
2.16 Automatic Reclosing System 79
252
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...