inputs. If the device features a sensitive ground current input (measuring range starts at 1 mA), the ground
fault protection always uses the calculated variable 3I0. In this case, parameter 613
50N/51N/67N w.
is not
available.
Voltage Protection (Protection Operating Quantities)
In a three-phase connection, the fundamental harmonic of the largest of the three phase-to-phase voltages
(
Vphph
) or phase-to-ground voltages (
Vph-n
) or the positive sequence voltage (
V1
) or the negative sequence
voltage (
V2
) is supplied to the overvoltage protection elements. In three-phase connection, undervoltage
protection relies either on the positive sequence voltage (
V1
) or the smallest of the phase-to-phase voltages
(
Vphph
) or the phase-to-ground voltages (
Vph-n
). This is configured by setting the parameter value in
address 614
OP. QUANTITY 59
and 615
OP. QUANTITY 27
. With single-phase voltage transformer
connection, a direct comparison of the measured quantities with the threshold values is carried out and the
parameterization of the characteristic quantity switchover is ignored.
Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
201
CT Starpoint
towards Line
towards Busbar
towards Line
CT Starpoint
202
Vnom PRIMARY
0.10 .. 800.00 kV
12.00 kV
Rated Primary Voltage
203
Vnom SECONDARY
100 .. 225 V
100 V
Rated Secondary Voltage
(L-L)
204
CT PRIMARY
10 .. 50000 A
100 A
CT Rated Primary Current
205
CT SECONDARY
1A
5A
1A
CT Rated Secondary
Current
206A
Vph / Vdelta
0.10 .. 3.00
1.73
Matching ratio Phase-VT To
Open-Delta-VT
207
Vnom-PRI VT V4
0.10 .. 800.00 kV
12.00 kV
VT Rated Primary Voltage
V4
208
Vnom-SEC VT V4
100 .. 225 V
100 V
VT Rated Secondary
Voltage V4
209
PHASE SEQ.
A B C
A C B
A B C
Phase Sequence
210A
TMin TRIP CMD
0.01 .. 32.00 sec
0.15 sec
Minimum TRIP Command
Duration
211A
TMax CLOSE CMD
0.01 .. 32.00 sec
1.00 sec
Maximum Close Command
Duration
212
BkrClosed I MIN
1A
0.04 .. 1.00 A
0.04 A
Closed Breaker Min.
Current Threshold
5A
0.20 .. 5.00 A
0.20 A
213
VT Connect. 3ph
Van, Vbn, Vcn
Vab, Vbc, VGnd
Vab, Vbc, Vx
Van,Vbn,Vcn,VGn
Van,Vbn,Vcn,VSy
Van,Vbn,Vcn,Vx
Van, Vbn, Vcn
VT Connection, three-
phase
214
Rated Frequency
50 Hz
60 Hz
50 Hz
Rated Frequency
215
Distance Unit
km
Miles
km
Distance measurement
unit
2.1.3.3
Functions
2.1 General
46
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...