Addr.
Parameter
C
Setting Options
Default Setting
Comments
3117
50Ns-1 PICKUP
1A
0.05 .. 35.00 A
2.00 A
50Ns-1 Pickup
5A
0.25 .. 175.00 A
10.00 A
3118
50Ns-1 DELAY
0.00 .. 320.00 sec; ∞
2.00 sec
50Ns-1 Time delay
3119
51Ns PICKUP
0.001 .. 1.400 A
0.100 A
51Ns Pickup
3119
51Ns PICKUP
1A
0.05 .. 4.00 A
1.00 A
51Ns Pickup
5A
0.25 .. 20.00 A
5.00 A
3119
51Ns PICKUP
0.003 .. 0.500 A
0.004 A
51Ns Pickup
3120
51NsTIME DIAL
0.05 .. 4.00 sec; ∞
1.00 sec
51Ns Time Dial
3120
51c TIME DIAL
0.50 .. 15.00 ; ∞
5.00
51c Time dial
3121A
50Ns T DROP-OUT
0.00 .. 60.00 sec
0.00 sec
50Ns Drop-Out Time Delay
3122
67Ns-1 DIRECT.
Forward
Reverse
Non-Directional
Forward
67Ns-1 Direction
3123
RELEASE DIRECT.
0.001 .. 1.200 A
0.010 A
Release directional element
3123
RELEASE DIRECT.
1A
0.05 .. 30.00 A
0.50 A
Release directional element
5A
0.25 .. 150.00 A
2.50 A
3124
PHI CORRECTION
-45.0 .. 45.0 °
0.0 °
Correction Angle for Dir.
Determination
3125
MEAS. METHOD
COS φ
SIN φ
COS φ
Measurement method for
Direction
3126
RESET DELAY
0 .. 60 sec
1 sec
Reset Delay
3127
51Ns I T min
0.003 .. 1.400 A
1.333 A
51Ns Current at const.
Time Delay T min
3127
51Ns I T min
1A
0.05 .. 20.00 A
15.00 A
51Ns Current at const.
Time Delay T min
5A
0.25 .. 100.00 A
75.00 A
3128
51Ns I T knee
0.003 .. 0.650 A
0.040 A
51Ns Current at Knee Point
3128
51Ns I T knee
1A
0.05 .. 17.00 A
5.00 A
51Ns Current at Knee Point
5A
0.25 .. 85.00 A
25.00 A
3129
51Ns T knee
0.20 .. 100.00 sec
23.60 sec
51Ns Time Delay at Knee
Point
3130
PU CRITERIA
Vgnd OR INs
Vgnd AND INs
Vgnd OR INs
Sensitive Ground Fault
PICKUP criteria
3131
M.of PU TD
1.00 .. 20.00 MofPU; ∞
0.01 .. 999.00 TD
Multiples of PU Time-Dial
3132
51Ns TD
0.05 .. 1.50
0.20
51Ns Time Dial
3140
51Ns Tmin
0.00 .. 30.00 sec
1.20 sec
51Ns Minimum Time Delay
3140
51Ns T min
0.10 .. 30.00 sec
0.80 sec
51Ns Minimum Time Delay
3141
51Ns Tmax
0.00 .. 30.00 sec
5.80 sec
51Ns Maximum Time Delay
3141
51Ns T max
0.50 .. 200.00 sec
93.00 sec
51Ns Maximum Time Delay
(at 51Ns PU)
3142
51Ns TIME DIAL
0.05 .. 15.00 sec; ∞
1.35 sec
51Ns Time Dial
3143
51Ns Startpoint
1.0 .. 4.0
1.1
51Ns Start Point of Inverse
Charac.
3144
51Ns IEC CURVE
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse
IEC Curve
Functions
2.13 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
222
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...