Addr.
Parameter
C
Setting Options
Default Setting
Comments
3145
51Ns ANSI CURVE
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse
ANSI Curve
3146
51Ns Drop-out
Instantaneous
Disk Emulation
Disk Emulation
Drop-out characteristic
3150
50Ns-2 Vmin
10.0 .. 90.0 V
10.0 V
50Ns-2 minimum voltage
3150
50Ns-2 Vmin
1.8 .. 50.0 V
2.0 V
50Ns-2 minimum voltage
3150
50Ns-2 Vmin
0.4 .. 50.0 V
2.0 V
50Ns-2 minimum voltage
3151
50Ns-2 Phi
-180.0 .. 180.0 °
-90.0 °
50Ns-2 angle phi
3152
50Ns-2 DeltaPhi
0.0 .. 180.0 °
30.0 °
50Ns-2 angle delta phi
3153
50Ns-1 Vmin
10.0 .. 90.0 V
15.0 V
50Ns-1 minimum voltage
3153
50Ns-1 Vmin
1.8 .. 50.0 V
6.0 V
50Ns-1 minimum voltage
3153
50Ns-1 Vmin
0.4 .. 50.0 V
6.0 V
50Ns-1 minimum voltage
3154
50Ns-1 Phi
-180.0 .. 180.0 °
-160.0 °
50Ns-1 angle phi
3155
50Ns-1 DeltaPhi
0.0 .. 180.0 °
100.0 °
50Ns-1 angle delta phi
3160
α1 red.dir.area
1 .. 15 °
2 °
Alpha1 (reduction direc-
tional area)
3161
α2 red.dir.area
1 .. 15 °
2 °
Alpha2 (reduction direc-
tional area)
Information List
No.
Information
Type of
Informa-
tion
Comments
1201
>BLOCK 64
SP
>BLOCK 64
1202
>BLOCK 50Ns-2
SP
>BLOCK 50Ns-2
1203
>BLOCK 50Ns-1
SP
>BLOCK 50Ns-1
1204
>BLOCK 51Ns
SP
>BLOCK 51Ns
1207
>BLK 50Ns/67Ns
SP
>BLOCK 50Ns/67Ns
1211
50Ns/67Ns OFF
OUT
50Ns/67Ns is OFF
1212
50Ns/67Ns ACT
OUT
50Ns/67Ns is ACTIVE
1215
64 Pickup
OUT
64 displacement voltage pick up
1217
64 TRIP
OUT
64 displacement voltage element TRIP
1221
50Ns-2 Pickup
OUT
50Ns-2 Pickup
1223
50Ns-2 TRIP
OUT
50Ns-2 TRIP
1224
50Ns-1 Pickup
OUT
50Ns-1 Pickup
1226
50Ns-1 TRIP
OUT
50Ns-1 TRIP
1227
51Ns Pickup
OUT
51Ns picked up
1229
51Ns TRIP
OUT
51Ns TRIP
1230
Sens. Gnd block
OUT
Sensitive ground fault detection BLOCKED
1264
IEEa =
VI
Corr. Resistive Earth current
1265
IEEr =
VI
Corr. Reactive Earth current
2.13.6
Functions
2.13 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
SIPROTEC 4, 7SJ62/64, Manual
223
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...