Figure 2-84
Activation of the sensitive ground-fault detection for cos-
ϕ
-/sin-
ϕ
measurement
Generation of a pickup message, for both current elements, is dependent on the direction selection for each
element and the setting of parameters 3130
PU CRITERIA
. If the element is set to
Non-Directional
and
parameter
PU CRITERIA
=
Vgnd OR INs
, a pickup message is generated as soon as the current threshold is
exceeded, irrespective of the status of the V0 element. If, however, the setting of parameter
PU CRITERIA
is
Vgnd AND INs
, the V
0
–element must have picked up also for non-directional mode.
However, if a direction is programmed, the current element must be picked up and the direction determina-
tion results must be present to generate a message. Once again, a condition for valid direction determination
is that the voltage element V
0
be picked up.
Parameter
PU CRITERIA
specifies, whether a fault is generated by means of the AND-function or the ORcom-
bination of displacement voltage and pickup of the ground current. The former may be advantageous if the
pickup setting of displacement voltage element V
0
was chosen to be very low.
Functions
2.13 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
204
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...