Protocol
Transmittable measuring range, format
IEC 61850
The primary operational measured values are transmitted.
The measured values as well as their unit format are set out in detail in manual PIXIT
7SJ.
The measured values are transmitted in “Float” format. The transmitted measuring
range is not limited and corresponds to the operational measurement.
PROFIBUS, Modbus,
DNP 3.0
DNP3 TCP
PROFINET
The unit format of the measured values on the device side is at first automatically
generated by means of the selected nominal values of current and voltage within the
system data.
The current unit format can be determined in DIGSI or at the device via Menu Opera-
tional Values.
The user can select via DIGSI which operational measured values (primary, secondary
or percentage) must be transmitted.
The measured values are always transmitted as 16-bit values including sign (range ±
32768). The user can define the scaling of the operational measured value to be trans-
mitted. This will result in the respective transmittable measuring range.
For further details, please refer to the descriptions and protocol profiles.
Information List
No.
Information
Type of
Informa-
tion
Comments
268
Superv.Pressure
OUT
Supervision Pressure
269
Superv.Temp.
OUT
Supervision Temperature
601
Ia =
MV
Ia
602
Ib =
MV
Ib
603
Ic =
MV
Ic
604
In =
MV
In
605
I1 =
MV
I1 (positive sequence)
606
I2 =
MV
I2 (negative sequence)
621
Va =
MV
Va
622
Vb =
MV
Vb
623
Vc =
MV
Vc
624
Va-b=
MV
Va-b
625
Vb-c=
MV
Vb-c
626
Vc-a=
MV
Vc-a
627
VN =
MV
VN
629
V1 =
MV
V1 (positive sequence)
630
V2 =
MV
V2 (negative sequence)
632
Vsync =
MV
Vsync (synchronism)
641
P =
MV
P (active power)
642
Q =
MV
Q (reactive power)
644
Freq=
MV
Frequency
645
S =
MV
S (apparent power)
661
Θ REST. =
MV
Threshold of Restart Inhibit
701
INs Real
MV
Resistive ground current in isol systems
702
INs Reac
MV
Reactive ground current in isol systems
805
Θ Rotor
MV
Temperature of Rotor
807
Θ/Θtrip
MV
Thermal Overload
809
T reclose=
MV
Time untill release of reclose-blocking
2.25.3.3
Functions
2.25 Auxiliary Functions
332
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...