Power Off All Devices & Install Storm Trapper
1
2
WARNING:
If wires are to be buried or covered, use conduit to protect the wires.
(Continued on back)
The following procedures are general steps for a typical installation. For additional information, please contact Technical
Support at 1-800-229-3404 or [email protected].
1
Ensure power has been terminated on rectifier and all devices.
2
Install
Storm Trapper HE Surge Arrester
on
AC
input:
a
Install black leads across
Line 1 and Line 2
of rectifier’s
AC
input.
These lines should be routed to the breaker.
b
Connect white lead to rectifier chassis.
NOTE:
If an arrestor is already installed on the
AC
input, then install the
Storm
Trapper HE Surge Arrester
in parallel. Replace spade terminals with flat
terminals for easier connection to where existing arrester is connected.
4
Secure
Storm Trapper HE Surge Arrester
by zip-tie to suitable location or
place on floor of rectifier.
Installing the Surge Arrester Kit
WARNING
:
To prevent electrostatic discharge (ESD) damage when handling electronic equipment, always wear an anti-static
wrist strap attached to an unpainted, grounded metal object. Ensure the wrist strap has maximum contact with bare skin.
Install DC Lightning Arrestor & Surge Detector
1
Attach
DC Lightning Arrestor
’s black leads
to rectifier
DC
outputs.
2
Thread
DC Lightning Arrestor’
s white wire through the hole (marked
Pulse
) on
the
Surge Detector’
s current transformer.
3
Connect a spade connector (included in kit) to the end of the
DC Lightning
Arrestor
’s white wire and connect to common ground location.
4
Wire and connect the
Surge Detector
to the Bullhorn RMU’s digital
Channel 5
. Be
sure to observe proper polarity.
5
Connect
DC Lightning Arrestor
’s two yellow wires to Bullhorn RMU’s
Channel 6
.
Polarity is not important as long as one wire is on the positive input and the other is
on the negative input.
6
DC Lightning Arrestor
can be placed on rectifier floor or anywhere to keep the
installation tidy.
Surge Detector
DC Lightning Arrestor
Storm Trapper HE
Surge Arrester
NOTE:
For rectifier types other than
JA
—
If a non-Delta high energy surge arrestor is already installed on the
AC
input, you
do not
need to install the
Storm Trapper HE Surge Arrester
.
RM4010
Installation and Configuration
Quick Reference Guide
Part No. 122248-000 Rev. 1
1 of 2
April 2020
Required Tools
Lightning Arrester Surge Kit
Quick Reference Guide
Field Update Tool (FUT)
Windows
®
Laptop PC
USB Mini-b cable
Bullhorn
®
Tools configuration software
Installation tools
Optional Items
Hook-up wire for field installation
Ground rod and copper wire