Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
1520A 67-2 MEASUREM.
67 Direct. O/C
Fundamental
True RMS
Fundamental
67-2 measurement of
1521A 67-1 MEASUREM.
67 Direct. O/C
Fundamental
True RMS
Fundamental
67-1 measurement of
1522A 67-TOC MEASUR.
67 Direct. O/C
Fundamental
True RMS
Fundamental
67-TOC measurement of
1523 67-2 Direction
67 Direct. O/C
Forward
Reverse
Non-Directional
Forward
67-2 Direction
1524 67-1 Direction
67 Direct. O/C
Forward
Reverse
Non-Directional
Forward
67-1 Direction
1525 67-TOC Direct.
67 Direct. O/C
Forward
Reverse
Non-Directional
Forward
67-TOC Direction
1526 67-3 Direction
67 Direct. O/C
Forward
Reverse
Non-Directional
Forward
67-3 Direction
1527A 67-3 MEASUREM.
67 Direct. O/C
Fundamental
True RMS
Fundamental
67-3 measurement of
1528 67-3 PICKUP
67 Direct. O/C
1A
1.00 .. 35.00 A; ∞
∞ A
67-3 Pickup
5A
5.00 .. 175.00 A; ∞ ∞ A
1529 67-3 DELAY
67 Direct. O/C
0.00 .. 60.00 sec; ∞ 0.00 sec
67-3 Time Delay
1530 67
67 Direct. O/C
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
67
1531 MofPU Res T/Tp
67 Direct. O/C
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
Multiple of Pickup <->
T/Tp
1532A 67-3 active
67 Direct. O/C
always
with 79 active
always
67-3 active
1601 FCT 67N/67N-TOC 67 Direct. O/C
OFF
ON
OFF
67N, 67N-TOC Ground
Time Overcurrent
1602 67N-2 PICKUP
67 Direct. O/C
1A
0.05 .. 35.00 A; ∞
0.50 A
67N-2 Pickup
5A
0.25 .. 175.00 A; ∞ 2.50 A
1603 67N-2 DELAY
67 Direct. O/C
0.00 .. 60.00 sec; ∞ 0.10 sec
67N-2 Time Delay
1604 67N-1 PICKUP
67 Direct. O/C
1A
0.05 .. 35.00 A; ∞
0.20 A
67N-1 Pickup
5A
0.25 .. 175.00 A; ∞ 1.00 A
1605 67N-1 DELAY
67 Direct. O/C
0.00 .. 60.00 sec; ∞ 0.50 sec
67N-1 Time Delay
1607 67N-TOC PICKUP
67 Direct. O/C
1A
0.05 .. 4.00 A
0.20 A
67N-TOC Pickup
5A
0.25 .. 20.00 A
1.00 A
1608 67N-TOC T-DIAL
67 Direct. O/C
0.05 .. 3.20 sec; ∞
0.20 sec
67N-TOC Time Dial
1609 67N-TOC T-DIAL
67 Direct. O/C
0.50 .. 15.00 ; ∞
5.00
67N-TOC Time Dial
1610 67N-TOC DropOut 67 Direct. O/C
Instantaneous
Disk Emulation
Disk Emulation
Drop-Out Characteristic
1611 67N-TOC IEC
67 Direct. O/C
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse
IEC Curve
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SJ62/64, Manual
625
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...