Figure 2-134
Logic diagram of temperature processing for the RTD box
Setting Notes
General
Temperature detection is only effective and accessible if this protection function was allocated to an interface
during configuration (Section
). At address 190
RTD-BOX INPUT
the RTD box is allo-
cated to the interface at which it will be operated (e.g. port C). The number of sensor inputs and the commu-
nication mode were set at address 191
RTD CONNECTION
. The temperature unit (°C or °F) was set in the
Power System Data 1 at address
TEMP. UNIT
.
If the RTD box is operated in half-duplex mode, the flow control (CTS) must be selected by means of a plug-in
jumper (see Section
in the Chapter “Mounting and Commissioning”) “/CTS
enabled by /RTS”.
Device Settings
The settings are the same for each input and are here shown at the example of measuring input 1.
Set the type of temperature sensor for RTD 1 (temperature sensor for measuring point 1) at address 9011
RTD
1 TYPE
. You can choose between ,
Ni 120 Ω
and
Ni 100 Ω
. If no measuring point is available for RTD 1,
set
RTD 1 TYPE
=
Not connected
. This setting is only possible in DIGSI at “Display Additional Settings”.
Address 9012
RTD 1 LOCATION
informs the device on the mounting location of RTD 1. You can choose
between
Oil
,
Ambient
,
Winding
,
Bearing
and
Other
. The selection is not evaluated in the device but
only serves the purpose of providing information about the medium in which the temperature measurement
is carried out. This setting is only possible in DIGSI at “Display Additional Settings”.
You can also set an alarm temperature and a tripping temperature. Depending on the temperature unit
selected in the Power System Data (Section
in address 276
TEMP. UNIT
), the alarm
temperature can be expressed in degrees Celsius (°C) (address 9013
RTD 1 STAGE 1
) or degrees Fahrenheit
(°F) (address 9014
RTD 1 STAGE 1
). The tripping temperature is set to degrees Celsius (°C) in address 9015
RTD 1 STAGE 2
or to degrees Fahrenheit (°F) at address 9016
RTD 1 STAGE 2
.
Accordingly, you can enter the settings for all connected temperature sensors of the RTD box.
2.22.2
Functions
2.22 Temperature Detection via RTD Boxes
SIPROTEC 4, 7SJ62/64, Manual
307
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...