Jumper
Nominal Voltage
DC 24 V/ 48 V
DC 60 V to 125 V
DC 110 V to 250 V,
AC 115 V to 230 V
X53
Not used
1-2
2-3
cannot be changed
interchangeable
Pickup Voltages of BI1 to BI3
Table 3-5
Jumper settings for the pickup voltages of the binary inputs BI1 to BI3 on the processor board
A–CPU for 7SJ62.../EE
Binary Inputs
Jumper
DC 19 V Pickup
1)
DC 88 V Pickup
3)
BI1
X21
L
H
BI2
X22
L
H
BI3
X23
L
H
1)
Factory settings for devices with power supply voltages of DC 24 V to 125 V
2)
Factory settings for devices with power supply voltages of DC 110 V to 220 V and AC 115 V/ 230 V
Contact Mode for Binary Outputs BO1 and BO2
Table 3-6
Jumper settings for the contact mode of the relays BO1 to BO2 on the processor board A–CPU
for7SJ62.../EE
for
Jumper
Open in quiescent state
(NO)
Closed in quiescent state
(NC)
Presetting
BO1
X41
1-2
2-3
1-2
BO2
X42
1-2
2-3
1-2