Addr.
Parameter
Setting Options
Default Setting
Comments
6140
SYNC PERMIS.
YES
NO
YES
Switching at synchronous condi-
tions
6141
F SYNCHRON
0.01 .. 0.04 Hz
0.01 Hz
Frequency threshold ASYN <-->
SYN
6142
dV SYNC V2>V1
0.5 .. 50.0 V
5.0 V
Maximum voltage difference
V2>V1
6143
dV SYNC V2<V1
0.5 .. 50.0 V
5.0 V
Maximum voltage difference
V2<V1
6144
dα SYNC α2> α1
2 .. 80 °
10 °
Maximum angle difference
alpha2>alpha1
6145
dα SYNC α2< α1
2 .. 80 °
10 °
Maximum angle difference
alpha2<alpha1
6146
T SYNC-DELAY
0.00 .. 60.00 sec
0.00 sec
Release delay at synchronous
conditions
6150
dV SYNCHK V2>V1
0.5 .. 50.0 V
5.0 V
Maximum voltage difference
V2>V1
6151
dV SYNCHK V2<V1
0.5 .. 50.0 V
5.0 V
Maximum voltage difference
V2<V1
6152
df SYNCHK f2>f1
0.01 .. 2.00 Hz
0.10 Hz
Maximum frequency difference
f2>f1
6153
df SYNCHK f2<f1
0.01 .. 2.00 Hz
0.10 Hz
Maximum frequency difference
f2<f1
6154
dα SYNCHK α2>α1
2 .. 80 °
10 °
Maximum angle difference
alpha2>alpha1
6155
dα SYNCHK α2<α1
2 .. 80 °
10 °
Maximum angle difference
alpha2<alpha1
Information List
No.
Information
Type of
Informa-
tion
Comments
170.0001 >25-1 act
SP
>25-group 1 activate
170.0043 >25 Sync req.
SP
>25 Synchronization request
170.0049 25 CloseRelease
OUT
25 Sync. Release of CLOSE Command
170.0050 25 Sync. Error
OUT
25 Synchronization Error
170.0051 25-1 BLOCK
OUT
25-group 1 is BLOCKED
170.2007 25 Measu. req.
SP
25 Sync. Measuring request of Control
170.2008 >BLK 25-1
SP
>BLOCK 25-group 1
170.2009 >25direct CO
SP
>25 Direct Command output
170.2011 >25 Start
SP
>25 Start of synchronization
170.2012 >25 Stop
SP
>25 Stop of synchronization
170.2013 >25 V1>V2<
SP
>25 Switch to V1> and V2<
170.2014 >25 V1<V2>
SP
>25 Switch to V1< and V2>
170.2015 >25 V1<V2<
SP
>25 Switch to V1< and V2<
170.2016 >25 synchr.
SP
>25 Switch to Sync
170.2022 25-1 meas.
OUT
25-group 1: measurement in progress
170.2025 25 MonTimeExc
OUT
25 Monitoring time exceeded
170.2026 25 Synchron
OUT
25 Synchronization conditions okay
170.2027 25 V1> V2<
OUT
25 Condition V1>V2< fulfilled
2.21.1.10
Functions
2.21 Synchronization Function
304
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...