Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
6413A 25 Synchron
SYNC function
4
YES
NO
YES
Switching at synchronous
condition
6420 T-CB close
SYNC function
4
0.01 .. 0.60 sec
0.06 sec
Closing (operating) time
of CB
6421 Balancing V1/V2
SYNC function
4
0.50 .. 2.00
1.00
Balancing factor V1/V2
6422A ANGLE ADJUSTM.
SYNC function
4
0 .. 360 °
0 °
Angle adjustment (trans-
former)
6423 CONNECTIONof V2 SYNC function
4
A-G
B-G
C-G
A-B
B-C
C-A
A-B
Connection of V2
6425 VT Vn2, primary
SYNC function
4
0.10 .. 800.00 kV
12.00 kV
VT nominal voltage V2,
primary
6430 dV ASYN V2>V1
SYNC function
4
0.5 .. 50.0 V
2.0 V
Maximum voltage differ-
ence V2>V1
6431 dV ASYN V2<V1
SYNC function
4
0.5 .. 50.0 V
2.0 V
Maximum voltage differ-
ence V2<V1
6432 df ASYN f2>f1
SYNC function
4
0.01 .. 2.00 Hz
0.10 Hz
Maximum frequency
difference f2>f1
6433 df ASYN f2<f1
SYNC function
4
0.01 .. 2.00 Hz
0.10 Hz
Maximum frequency
difference f2<f1
6440 SYNC PERMIS.
SYNC function
4
YES
NO
YES
Switching at synchronous
conditions
6441 F SYNCHRON
SYNC function
4
0.01 .. 0.04 Hz
0.01 Hz
Frequency threshold
ASYN <--> SYN
6442 dV SYNC V2>V1
SYNC function
4
0.5 .. 50.0 V
5.0 V
Maximum voltage differ-
ence V2>V1
6443 dV SYNC V2<V1
SYNC function
4
0.5 .. 50.0 V
5.0 V
Maximum voltage differ-
ence V2<V1
6444 dα SYNC α2> α1
SYNC function
4
2 .. 80 °
10 °
Maximum angle differ-
ence alpha2>alpha1
6445 dα SYNC α2< α1
SYNC function
4
2 .. 80 °
10 °
Maximum angle differ-
ence alpha2<alpha1
6446 T SYNC-DELAY
SYNC function
4
0.00 .. 60.00 sec
0.00 sec
Release delay at synchro-
nous conditions
6450 dV SYNCHK V2>V1 SYNC function
4
0.5 .. 50.0 V
5.0 V
Maximum voltage differ-
ence V2>V1
6451 dV SYNCHK V2<V1 SYNC function
4
0.5 .. 50.0 V
5.0 V
Maximum voltage differ-
ence V2<V1
6452 df SYNCHK f2>f1
SYNC function
4
0.01 .. 2.00 Hz
0.10 Hz
Maximum frequency
difference f2>f1
6453 df SYNCHK f2<f1
SYNC function
4
0.01 .. 2.00 Hz
0.10 Hz
Maximum frequency
difference f2<f1
6454 dα SYNCHK α2>α1 SYNC function
4
2 .. 80 °
10 °
Maximum angle differ-
ence alpha2>alpha1
6455 dα SYNCHK α2<α1 SYNC function
4
2 .. 80 °
10 °
Maximum angle differ-
ence alpha2<alpha1
Functions, Settings, Information
F.2 Settings
642
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...