Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
3107 VPH MAX
Sens. Gnd Fault
10 .. 100 V
75 V
L-Gnd Voltage of
Unfaulted Phase Vph Max
3108 64-1 VGND
Sens. Gnd Fault
1.8 .. 200.0 V; ∞
40.0 V
64-1 Ground Displace-
ment Voltage
3109 64-1 VGND
Sens. Gnd Fault
1.8 .. 170.0 V; ∞
40.0 V
64-1 Ground Displace-
ment Voltage
3110 64-1 VGND
Sens. Gnd Fault
10.0 .. 225.0 V; ∞
70.0 V
64-1 Ground Displace-
ment Voltage
3111 T-DELAY Pickup
Sens. Gnd Fault
0.00 .. 320.00 sec;
∞
1.00 sec
Time-DELAY Pickup
3112 64-1 DELAY
Sens. Gnd Fault
0.10 ..
40000.00 sec; ∞
10.00 sec
64-1 Time Delay
3113 50Ns-2 PICKUP
Sens. Gnd Fault
0.001 .. 1.500 A
0.300 A
50Ns-2 Pickup
3113 50Ns-2 PICKUP
Sens. Gnd Fault 1A
0.05 .. 35.00 A
10.00 A
50Ns-2 Pickup
5A
0.25 .. 175.00 A
50.00 A
3114 50Ns-2 DELAY
Sens. Gnd Fault
0.00 .. 320.00 sec;
∞
1.00 sec
50Ns-2 Time Delay
3115 67Ns-2 DIRECT
Sens. Gnd Fault
Forward
Reverse
Non-Directional
Forward
67Ns-2 Direction
3117 50Ns-1 PICKUP
Sens. Gnd Fault
0.001 .. 1.500 A
0.100 A
50Ns-1 Pickup
3117 50Ns-1 PICKUP
Sens. Gnd Fault 1A
0.05 .. 35.00 A
2.00 A
50Ns-1 Pickup
5A
0.25 .. 175.00 A
10.00 A
3118 50Ns-1 DELAY
Sens. Gnd Fault
0.00 .. 320.00 sec;
∞
2.00 sec
50Ns-1 Time delay
3119 51Ns PICKUP
Sens. Gnd Fault
0.001 .. 1.400 A
0.100 A
51Ns Pickup
3119 51Ns PICKUP
Sens. Gnd Fault
0.003 .. 0.500 A
0.004 A
51Ns Pickup
3119 51Ns PICKUP
Sens. Gnd Fault 1A
0.05 .. 4.00 A
1.00 A
51Ns Pickup
5A
0.25 .. 20.00 A
5.00 A
3120 51NsTIME DIAL
Sens. Gnd Fault
0.05 .. 4.00 sec; ∞
1.00 sec
51Ns Time Dial
3120 51c TIME DIAL
Sens. Gnd Fault
0.50 .. 15.00 ; ∞
5.00
51c Time dial
3121A 50Ns T DROP-OUT
Sens. Gnd Fault
0.00 .. 60.00 sec
0.00 sec
50Ns Drop-Out Time
Delay
3122 67Ns-1 DIRECT.
Sens. Gnd Fault
Forward
Reverse
Non-Directional
Forward
67Ns-1 Direction
3123 RELEASE DIRECT.
Sens. Gnd Fault
0.001 .. 1.200 A
0.010 A
Release directional
element
3123 RELEASE DIRECT.
Sens. Gnd Fault 1A
0.05 .. 30.00 A
0.50 A
Release directional
element
5A
0.25 .. 150.00 A
2.50 A
3124 PHI CORRECTION
Sens. Gnd Fault
-45.0 .. 45.0 °
0.0 °
Correction Angle for Dir.
Determination
3125 MEAS. METHOD
Sens. Gnd Fault
COS φ
SIN φ
COS φ
Measurement method for
Direction
3126 RESET DELAY
Sens. Gnd Fault
0 .. 60 sec
1 sec
Reset Delay
3127 51Ns I T min
Sens. Gnd Fault
0.003 .. 1.400 A
1.333 A
51Ns Current at const.
Time Delay T min
3127 51Ns I T min
Sens. Gnd Fault 1A
0.05 .. 20.00 A
15.00 A
51Ns Current at const.
Time Delay T min
5A
0.25 .. 100.00 A
75.00 A
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SJ62/64, Manual
629
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...