Function Module
Explanation
Task Level
MW_
BEARB
PLC1_
BEARB
PLC_
BEARB
SFS_
BEARB
OR
OR - Gate
X
X
X
X
REAL_TO_DINT
Adaptor
X
X
X
X
REAL_TO_INT
Conversion
X
X
X
X
REAL_TO_UINT
Conversion
X
X
X
X
RISE_DETECT
Rise detector
X
X
X
X
RS_FF
RS- Flipflop
—
X
X
X
RS_FF_MEMO
RS- Flipflop with state memory
—
X
X
X
SQUARE_ROOT
Root Extractor
X
X
X
X
SR_FF
SR- Flipflop
—
X
X
X
SR_FF_MEMO
SR- Flipflop with state memory
—
X
X
X
ST_AND
AND gate with status
X
X
X
X
ST_NOT
Inverter with status
X
X
X
X
ST_OR
OR gate with status
X
X
X
X
SUB
Substraction
X
X
X
X
TIMER
Timer
—
X
X
—
TIMER_SHORT
OR gate with status
—
X
X
—
UINT_TO_REAL
Conversion
X
X
X
X
UPPER_SETPOINT
Upper Limit
X
—
—
—
X_OR
XOR - Gate
X
X
X
X
ZERO_POINT
Zero Supression
X
—
—
—
Device-specific CFC Blocks
Table 4-1
BOSTATE – The block reads the state of an output relay and outputs it as a Boolean value.
Name
Type
Description
Default function
Input
BO
UINT
Number of output relay
0
Number
STATE
BOOL
State of the output relay
FALSE
Task levels:
Recommendation: This block should be placed in the MW_BEARB level,
where it is cyclically updated
Note: In the task levels PLC1_BEARB and PLC_BEARB, changes of the
output relay are no trigger events for these levels. These levels are only
triggered by changes to indications routed onto them.
Behavior of inputs and outputs:
If the output relay with the number BO exists and the state of the associ-
ated output relay is active, STATE = TRUE is set, otherwise STATE =
FALSE.
Table 4-2
ASWITCH – This block is used to switch between two REAL inputs (RMS values).
Name
Type
Description
Default function
Input
SWITCH
BOOL
Analog value selection
FALSE
IN1
REAL
Analog value
0.0
IN2
REAL
Analog value
0.0
Output
OUT
REAL
Selected analog value
Technical Data
4.26 User-defined Functions (CFC)
SIPROTEC 4, 7SJ62/64, Manual
505
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...