Installing the Control System
2.3
Connecting the individual components
2-28
SINUMERIK 802S
6FC5 597–2AA00–0BP2 (01.02)
Signal level
RS422
Signal type
VO
Voltage output (supply)
I
5V input (5V signal)
Encoder types which can be connected
Incremental 5 V encoders can be connected directly.
Characteristics
The encoders must meet the following requirements:
Transmission method:
Differential transmission with 5 V square–wave
signals
Output signals:
Track A as true and negated signal (U
a1
, U
a1
)
Track B as true and negated signal (U
a2
, U
a2
)
Zero signal N as true and negated signal
(U
a0
, U
a0
)
Max. output frequency: 1.5 MHz
Phase offset between
tracks A and B:
90
°
"
30
°
Current consumption:
max. 300 mA
Cable lengths
The maximum cable length depends on the specification of the encoder supply and on the
transmission frequency. When using preassembled cables from SIEMENS, the following va-
lues may not be exceeded to ensure interference–free operation:
Table 2-9
Maximum cable length with respect to the encoder supply
Supply Voltage
Tolerance
Current
Consumption
Max.
Cable Length
5 V DC
4.75 V...5.25 V
< 300 mA
25 m
5 V DC
4.75 V...5.25 V
< 220 mA
35 m
Table 2-10
Maximum cable lengths with respect to the transmission frequency
Encoder Type
Frequency
Max. Cable Length
1 MHz
10 m
Incremental
500 kHz
35 m
Summary of Contents for SINUMERIK 802S
Page 1: ...Start Up 01 2002 Edition SINUMERIK 802S ...
Page 2: ......
Page 8: ...Table of Contents viii SINUMERIK 802S 6FC5 597 2AA00 0BP2 01 02 notice ...
Page 104: ...Start Up 4 7 Commissioning 4 104 SINUMERIK 802S 6FC5 597 2AA00 0BP2 01 02 ...
Page 170: ...Index Index 170 SINUMERIK 802S 6FC5 597 2AA00 0BP2 01 02 notice ...
Page 172: ......