Start-Up
4.3
Starting up the PLC
4-63
SINUMERIK 802S
6FC5 597–2AA00–0BP2 (01.02)
Alarm responses:
Bit0 – bit 5 = 0: Showalarm (default)
Bit0 = 1:
NC Start inhibited
Bit1 = 1:
Read–in disable
Bit2 = 1:
Feed disable for all axes
Bit3 = 1:
EMERGENCY STOP
Bit4 = 1:
PLC Stop
Bit5 =
Reserved
Cancel criteria: Bit6 + bit7 = 0: SELF–CLEARING alarm (default)
Bit6 = 1 :
CANCELCLEAR alarm
Bit7 = 1 :
POWERONCLEAR alarm
Alarm texts
The user has two possibilities to define his own alarms.
S
using the Edit PLC txt softkey (cf. “Operation, Programming”, Chapter 7)
S
using the Toolbox 802SC Text Manager
The procedure is described in the Toolbox readme file.
Alarm texts are structured as follows:
Alarm number Flag 1 Flag2 Text
Note
The text must be put in inverted commas (‘’ ‘’)! Adhere to the given text structure.
Table 4-5
Example
Alarm Number
Flag 1
Flag 2
Text
700000
0
0
“User alarm 1”
700000 0 0 ‘’’’ // 1st user alarm, text is assigned by the user
700001 0 0 ‘’’’ // 2nd user alarm, text is assigned by the user
700002 0 0 ‘’’’ // 3rd user alarm, text is assigned by the user
700003 0 0 ‘’’’ // 4th user alarm, text is assigned by the user
700004 0 0 ‘’’’ // 5th user alarm, text is assigned by the user
700005 0 0 ‘’’’ // 6th user alarm, text is assigned by the user
...
Summary of Contents for SINUMERIK 802S
Page 1: ...Start Up 01 2002 Edition SINUMERIK 802S ...
Page 2: ......
Page 8: ...Table of Contents viii SINUMERIK 802S 6FC5 597 2AA00 0BP2 01 02 notice ...
Page 104: ...Start Up 4 7 Commissioning 4 104 SINUMERIK 802S 6FC5 597 2AA00 0BP2 01 02 ...
Page 170: ...Index Index 170 SINUMERIK 802S 6FC5 597 2AA00 0BP2 01 02 notice ...
Page 172: ......